Product Overview
-
Product Snapshot Type Modular and stationary boiler house Range 0.5MW to 4MW Fuel Type Natural gas or diesel (dual fuel) Building Options Containerised or stationary Controls PLC with touchscreen, BMS interface Flue System Multiple stacks (as required) Flow Temperature (°C) Up to 95°C (higher temperatures available on request) Return Temperature (°C) 70°C (lower return for higher efficiency) Applications Commercial and industrial Our boiler houses are available as containerised units for fast delivery and easy installation, or as permanent plant rooms with a range of building and cladding options. All systems are fully integrated with pumps, controls, safety systems and are tested prior to dispatch.
-
Key Features
Up to 4MW CapacityStandard capacities from 0.5MW to 4MW.
Dual FuelCompatible with natural gas or diesel.
Building and Cladding OptionsModular containerised or stationary buildings with multiple cladding, insulation and roof options.
Code CompliantEngineered to AS, EN and local codes.
Standard Configurations
- Condensing or high efficiency boilers
- Dual fuel burner (natural gas / diesel)
- Gas train and pressure regulation
- Heating water pumps (duty/standby)
- Expansion vessel and system safety
- Controls and BMS interface
- Flue system (single or dual stack)
- Electrical power and distribution
- Fully enclosed building with insulation
- Factory testing and documentation
Optional Upgrades
- Higher flow temperature
- Weatherproof acoustic enclosure
- Remote monitoring
- Stainless steel pipework
- Additional pumps
- Alternative cladding finishes
- Fire detection and ventilation

Stationary Boiler Houses
- Pre-fabricated steel frame and steel cladding with or without insulation
- Fire Tube boilers – Built and designed in-house with modulating power burners for either dual fuel or natural gas operation
- 95ºC water available with plate heat exchangers, variable speed Primary and secondary pumps included



Building style
Type Variant Containerised Flat Roof Containerised Pitch Roof Stationary Steel Frame Stationary Architectural Cladding Cladding Options
Type Colorbond® Aluminium Architectural Insulated Panel -
Model 0.5MW 1MW 2MW 4MW Heat Output (kW) 500 1,000 2,000 4,000 Typical Boiler Configuration 1 x 500kW or
2 x 250kW2 x 500kW or
1 x 1,000kW2 x 1,000kW 4 x 1,000kW or
2 x 2,000kWFuel Options Natural gas or diesel (dual fuel) Heating Water Pumps Duty / Standby (high flow) Expansion Vessel Included Controls PLC with touchscreen, BMS interface Flue System Multiple stacks (as required) Flow Temperature (°C) Up to 95°C (higher temperatures available on request) Return Temperature (°C) 70°C (lower return for higher efficiency) Typical Flow Rate (L/s) (ΔT 20°C) 5.0 12.0 24.0 48.0 Typical Connections Heating Flow/return DN65 DN80 DN100 DN150 Gas Supply DN25 DN40 DN50 DN80 Diesel Supply DN25 DN25 DN32 DN40 Make-up Water DN20 DN20 DN25 DN22 Electrical Supply (400V) 63A 100A 200A 400A Footprint (L x W x H) m* 6.1 x 2.4 x 2.9 6.1 x 2.4 x 2.9 12.2 x 2.4 x 2.9 12.2 x 2.4 x 2.9 *Indicative dimensions for containerised units. Stationary buildings sized to suit project.
- ...
-